Friday, 16 December 2011

Reyrolle Circuit Breaker (DoH Estates Alert)


An incident occurred involving a Reyrolle 11kV SMV Hadrian circuit breaker rated at 630A. The concern is a flashover could occur while isolating the circuit breaker. This would be as a result of the busbar shutters dropping down onto the exposed metal bushings whilst in contact or close proximity to the live busbar or feeder contacts.
There may be a potential fault with design of the four split pins which are located to hold the shutter mechanism in place.
This estates and facilities alert, EFA/2011/006, explains that operators, service and maintenance providers should:
  • ensure the Reyrolle SMV Hadrian Circuit breaker is only withdrawn from the service position when both the busbar and feeder contacts have been made dead from a separate location
  • ensure the that a check is made on the four split pins which hold the busbar shutters in place
  • visually check all split pins and dowels on both ends of the feeder and busbar shutter mechanisms to ensure they are fully located in the hole in the dowel and the split pins are bent firmly round the dowel and they are orientated with the legs of the split pins in view. 
Operators, service and maintenance providers should contact the manufacturer to seek advice on an individual case by case basis.

Wednesday, 14 December 2011

EFA/2011/006 High-Voltage (HV) 11kV (Siemens) - Reyrolle Circuit Breaker - Hadrian (SMV) 630A (DoH Estates Alert)


The circuit breaker identified in this alert should only be withdrawn from the service position when both the busbar and feeder contacts are confirmed as dead
Please note: this document is for print purposes only, as it has not been fully tagged for accessibility.

Friday, 25 November 2011

Welsh Hospital Under Further Asbestos-Management Scrutiny

The Welsh Government has launched an independent review into the management of asbestos at Bronglais Hospital in Aberystwyth.

The hospital failed to implement effective controls to manage asbestos after a survey in 2004 found the substance in stairwells and lift shafts. The unsafe practices, which required maintenance workers to operate in these areas, continued until 2009, when they were quickly identified by the hospital’s new Health Board and reported to the HSE.

Friday, 28 October 2011

Electric Traction Lifts Without Motor Rooms. Also known as MRL Lifts (machine roomless lifts) (DoH Estates Alert)

The following Actions are required of NHS providers:
  • All MRL lift installations should include some form of electrical standby power (probably UPS) to facilitate passenger rescue by ensuring electrically operated brakes can be lifted and/or power provided to drive a lift to the nearest landing. 
  • All MRL lift installations should include a suitable system to monitor the condition of the UPS or battery and to raise alarms, where necessary.
  • The lift installer should provide confirmation from the UPS manufacturer that the UPS is suitable for the environment where they are located (e.g. lift shaft, plant rooms, etc.) and in particular meets all Electromagnetic compatibility (EMC) requirements.
  • Installation teams and healthcare providers should ensure that all emergency standby power and UPS equipment connected to an MRL lift are monitored by the healthcare premise Building Management System (BMS) or other suitable facility. 
For existing MRL lifts, healthcare providers should liaise with the lift installer to determine whether a link can be installed from the BMS/PC or suitable monitoring system to the lift UPS.

http://www.cftconsulting.co.uk/  

Monday, 24 October 2011

VIE (Vacuum insulated evaporator) Main Storage Vessel for Bulk Medical Oxygen Supply. (DoH Estates Alert)

There has been an uncontrolled release of liquid oxygen from a vacuum insulated evaporator (VIE) installed at an acute hospital in Wales. This resulted in the loss of approximately 7000 litres of liquid oxygen over a 45 minute period. The discharge was observed on CCTV cameras. If the CCTV had not been present the discharge may have gone unnoticed until the low level alarm activated for the system.